A dew point means nothing until you know the pressure it was measured at.
Convert a hygrometer reading to moisture content by volume and by mass, and find the dew or frost point the same gas has at the enclosure pressure. Frost or dew point, gauge or absolute, in bar, MPa, kPa or psi.
Moisture content for each dew or frost point at the sensor pressure entered above, and the dew or frost point the same gas would show at the target pressure. The table follows the calculator settings.
| Dew / frost point at sensor | Water vapour pressure | ppmv | ppmw | At target pressure |
|---|
Water in SF6 is present as a trace vapour. A hygrometer measures its dew or frost point: the temperature at which that vapour would start to condense at the pressure the sensor is sitting at. The moisture content follows from the partial pressure of water, and that is what lets a reading taken at one pressure be compared with a limit stated at another.
xw = e(Td) / psensor
ppmv = 106 · xw ppmw = ppmv · 18.015 / 146.06
e(Td2) = xw · ptarget → solve for Td2
e(T) is the saturation vapour pressure of water, over ice or over liquid water, from the equations of Sonntag (1990) on the ITS-90 temperature scale. Both pressures are converted to absolute on input and worked in pascals throughout. The converted dew or frost point is found by solving the same equation numerically. The implementation was checked against the Hyland–Wexler formulation at 5 °C intervals: agreement is within 0.09 % over water from −40 to +50 °C and within 0.11 % over ice down to −80 °C. At −40 °C a 0.1 % difference in vapour pressure is about 0.01 °C of dew point.
This tool converts between units; it does not tell you whether a reading is acceptable. Moisture limits are set by the equipment manufacturer and by the applicable IEC standards, and they differ between equipment types, between new gas and gas in service, and with the pressure the limit is quoted at. Check which unit and which pressure the limit uses before comparing.
Provided for reference and cross-checking. Does not replace equipment manufacturers' data, nameplate values or operating instructions, or the applicable standards. Version 1.0. Source: D. Sonntag, saturation vapour pressure formulations over water and ice, 1990.