Field calculation tool · Gas systems · GT-07

SF6 moisture: dew point, ppmv and pressure

A dew point means nothing until you know the pressure it was measured at.

Convert a hygrometer reading to moisture content by volume and by mass, and find the dew or frost point the same gas has at the enclosure pressure. Frost or dew point, gauge or absolute, in bar, MPa, kPa or psi.

Moisture conversion

°C
As read on the hygrometer.
Check the instrument setting. Most report frost point.
Gauge 0 = sensor vented to atmosphere.
Usually the enclosure filling pressure.
Applies to both pressures above.
kPa
Lower at altitude: about 90 kPa at 1000 m.
Moisture content — by volume
—
Moisture content — by mass
—
Dew / frost point at target pressure
—
01

Across the range

Moisture content for each dew or frost point at the sensor pressure entered above, and the dew or frost point the same gas would show at the target pressure. The table follows the calculator settings.

Dew / frost point at sensorWater vapour pressureppmvppmwAt target pressure
02

Method and scope

Water in SF6 is present as a trace vapour. A hygrometer measures its dew or frost point: the temperature at which that vapour would start to condense at the pressure the sensor is sitting at. The moisture content follows from the partial pressure of water, and that is what lets a reading taken at one pressure be compared with a limit stated at another.

xw = e(Td) / psensor
ppmv = 106 · xw    ppmw = ppmv · 18.015 / 146.06
e(Td2) = xw · ptarget  →  solve for Td2

e(T) is the saturation vapour pressure of water, over ice or over liquid water, from the equations of Sonntag (1990) on the ITS-90 temperature scale. Both pressures are converted to absolute on input and worked in pascals throughout. The converted dew or frost point is found by solving the same equation numerically. The implementation was checked against the Hyland–Wexler formulation at 5 °C intervals: agreement is within 0.09 % over water from −40 to +50 °C and within 0.11 % over ice down to −80 °C. At −40 °C a 0.1 % difference in vapour pressure is about 0.01 °C of dew point.

What this assumes

  • Ideal mixing. The enhancement factor, which raises the effective saturation pressure slightly in a compressed gas, is ignored. At filling pressures up to about 1 MPa this is an error of the order of 1 % in ppmv, well inside the uncertainty of a field hygrometer.
  • Frost point and dew point are not the same reading. Below 0 °C water can condense as ice or as supercooled liquid, and the two give different numbers for the same gas. At −40 °C at atmospheric pressure, 127 ppmv shows as a frost point of −40 °C, while a dew point of −40 °C corresponds to 188 ppmv. Set the toggle to match the instrument, or the result is wrong by tens of percent.
  • The pressure is the pressure at the sensor. Many portable hygrometers sample through a needle valve and measure at atmospheric pressure; in-line sensors measure at enclosure pressure. A dew point reported without the pressure it was measured at cannot be converted.
  • The sample is representative. Moisture desorbs from enclosure walls and from the sampling hose. A reading taken before the hose has dried out, or straight after filling, reads high and drifts down. Temperature matters too: the same enclosure gives a higher reading on a warm afternoon than on a cold morning.
  • Range. Dew and frost points from −80 to +20 °C. Pure SF6 is assumed for the ppmw figure; for mixtures the volume figure still holds, but the mass figure needs the mixture molar mass.

This tool converts between units; it does not tell you whether a reading is acceptable. Moisture limits are set by the equipment manufacturer and by the applicable IEC standards, and they differ between equipment types, between new gas and gas in service, and with the pressure the limit is quoted at. Check which unit and which pressure the limit uses before comparing.

Using it

  • Atmospheric reading to enclosure conditions. A portable instrument reads a frost point of −40 °C at atmospheric pressure. At an enclosure filling pressure of 0.6 MPa gauge the same gas has a frost point of about −21.6 °C. Same water content, 127 ppmv; only the pressure has changed. This is the comparison to make before deciding whether condensation inside the enclosure is possible on a cold night.
  • Dew point to ppmv. Where a limit is quoted in ppmv, enter the reading and its sensor pressure and read the volume figure directly. To convert between pressure units on their own, use the pressure unit converter.
  • Comparing two instruments. Two hygrometers that disagree are often measuring at different pressures, or one reports frost point and the other dew point. Convert both to ppmv before deciding which one is wrong.

Provided for reference and cross-checking. Does not replace equipment manufacturers' data, nameplate values or operating instructions, or the applicable standards. Version 1.0. Source: D. Sonntag, saturation vapour pressure formulations over water and ice, 1990.

—

About HVPACE

HVPACE is the trading name of Power Asset Condition Engineering Limited, a New Zealand-based supplier of test and diagnostic instruments and selected specialty equipment for high-voltage power systems, backed by hands-on engineering expertise in condition assessment and diagnostics.

Read our technical papers
Web hvpace.co.nz  ·  Technical papers papers.hvpace.co.nz  ·  Products products.hvpace.co.nz
Email [email protected]  ·  Phone +64 21 025 9607 4  ·  Auckland 0616, New Zealand

HVPACE is the trading name of Power Asset Condition Engineering Limited (NZBN 9422724), Auckland, New Zealand.